spc
   Turkce
AC/DC orange 2arrow UPS Systems
spc

 

 500 kVA UPS Systems

 
AC/DC UPS    UPSon - 33M Series
   500 kVA UPS Systems Technical Specifications
 Power ( kVA )

500 kVA

 Power ( kWatt )

400 kWatt

 Input Voltage

380 / 400 / 415 VAC ; 3 Phase, N

 Input Voltage Range

± 15%

 Input Frequency

50 / 60 Hz

 Input Frequency Range

± 10%

 Input Power Factor

> 0,85

 Output Power Factor

0,8

 Output Voltage

380 / 400 / 415 VAC ; 3 Phase, N

 Output Voltage Regulation

± 1% ( Static ) ; ± 5% ( Dynamic )

 Output Frequency

50 Hz / 60 Hz ( selectable )

 Frequency Stability

± 0,1% ( operation by battery ) ; ± 1% ( main synchron )

 Voltage Wave

Sinusoidal

 Total Harmonic Distortion

< 3% ( lineer load ) ; < 5% ( non-lineer load )

 Cold Start

No

 Total Efficiency

> 90%

 Crest Factor 3 : 1
 Transfer Time

0 msec.

 Battery Type

No maintenance battery

 Battery Unit

30

 Charge Voltage

405 VDC

 Deep Discharge Voltage

300 VDC

 Battery Test

Automatic and manuel battery test system

 Battery Charge Time

8 hours to 90% capacity after deep discharge

 Type

LCD Alphanumerical mini panel

 LCD Display

Input Voltage , Output Voltage , Battery Voltage, Battery Current, Output Frequency, Battery Charge Level, UPS Power, Load Percent, Synchron Case, Communication systems fault info.

 LED Display

Load on Bypass, Load on UPS, Alarms and operation by battery leds.

 Over Load Capacity

100% ~ 125% load 10 minutes ; 125% ~ 150% load 1 minute ; > 150% load on the bypass

 Short Circuit

a) Inverter mod: UPSis shutdown itself
b) Bypass mod : AC protection fuse is blow

 Over Heat

a) If main normale : UPS is cross to by-pass mode
b) If main voltage is not normale : UPS is cut output, Alarm on the LCD Display.

 Battery Low Level

Battery low alarm occurs on the LCD. Sound alarm is given after 15 second

 Visual and Auditory

Bypass alarm, mains fault, load on bypass, overload, mains failure, output voltage high / low, over temperature, battery voltage high/low, short circuit, fault inverter, battery test
( Buzzer can be Off.)

 Management

Dry contact info, RS232 Serial Port, TMON Software, remote control panel ( option ), SNMP and Megatec protocol ( option )

 Dry Contact Information

Load on inverter / Bypass, Operation battery / mains, Battery low / normale, emergency button

 HTTP / SNMP Harmony

Windows 95/98/NT/XP, UNIX, LINUX, NOVELL, Netware, OS/2, Netlite, XENIX, AIX, MS-DOS, HP-UX, SUN OS ( Software CD and cable )

 Noice Level

< 63 to 65 dB ( 1 Meter )

 Technologic

High frequency IGBT technology, PWM, True Online System, 2 Micro Pro. and high protection by driver

 Operation Temperature / Humidity

0 °C ~ +40 °C / Maximum 90%

 Cooliing

Fan

 Dimension WxHxD ( mm )

1100 x 1600 x 800

 Weight

~ 1170 kg

 

Security ( EN50091-1 ) / EMC ( EN50091-2 ) / IP Class ( IP 20 ) / VFI Class ( IEC62040-3 )

 

Parallel kit, SNMP kit, seperate main input, remote pannel, Philters, 12 Pulse rectifier, temperature control rectifier, RS485, ECO Mod.

Not: Yukar?da belirtilen tüm bilgiler referans te?kil etmesi amac? ile verilmi?tir. Üçüncü ki?ilere bildirmeksizin de?i?tirme hakk? sakl?d?r. ©2007
ACDC Electronic Systems Inc.

teklif Information Request
spc

Home Page  |  UPS Systems  |  Dry Batteries  |  Gel Batteries  |  Voltage Regulators

Battery Chargers  |  Technical Support  |  Power Calculation  |  Site Map  |  Contact

spc

AC/DC Electronic Systems Inc. - TURKEY

Phone: +90 212 320 2007   -   Email: info@acdc.com.tr

spcyears of experience